Disclaimer: By using this website, you agree to the Terms and Conditions of Use (last updated 10/31/15).

View document Print document

×

Search by parameters


You can specify any of the following parameters.

Hold CTRL to select multiple options or de-select options in a filter.


Search results


2768 products match the given parameters.

Alphabetical filter

All 0-9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z


PROTOMONT NSSHÖU 0.6/1 kV4×700,6/1 kV
PROTOMONT NSSHÖU 0.6/1 kV4×950,6/1 kV
PROTOMONT NSSHÖU 0.6/1 kV5×1.50,6/1 kV
PROTOMONT NSSHÖU 0.6/1 kV5×100,6/1 kV
PROTOMONT NSSHÖU 0.6/1 kV5×160,6/1 kV
PROTOMONT NSSHÖU 0.6/1 kV5×2.50,6/1 kV
PROTOMONT NSSHÖU 0.6/1 kV5×250,6/1 kV
PROTOMONT NSSHÖU 0.6/1 kV5×350,6/1 kV
PROTOMONT NSSHÖU 0.6/1 kV5×40,6/1 kV
PROTOMONT NSSHÖU 0.6/1 kV5×60,6/1 kV
PROTOMONT NSSHÖU 0.6/1 kV7×1.50,6/1 kV
PROTOMONT NSSHÖU 0.6/1 kV7×2.50,6/1 kV
PROTOMONT NSSHÖU 0.6/1 kV7×40,6/1 kV
PROTOMONT NSSHÖU 0.6/1 kV8×1.50,6/1 kV
QFC - 4FO Subscriber Cable
Riser Flextube cable Bend BrightXS 144F (12 x 12F)
Riser Flextube cable Bend BrightXS 48F (4 x 12F)
Riser Flextube cable Bend BrightXS 72F (6 x 12F)
SFC - Single Fibre Drop Cable 1F
SIENOPYR(120) (N)HX4GAF 0.6/1kV1×0.50,6/1 kV
SIENOPYR(120) (N)HX4GAF 0.6/1kV1×0.750,6/1 kV
SIENOPYR(120) (N)HX4GAF 0.6/1kV1×10,6/1 kV
SIENOPYR(120) (N)HX4GAF 0.6/1kV1×1.50,6/1 kV
SIENOPYR(120) (N)HX4GAF 0.6/1kV1×100,6/1 kV
SIENOPYR(120) (N)HX4GAF 0.6/1kV1×1200,6/1 kV
SIENOPYR(120) (N)HX4GAF 0.6/1kV1×1500,6/1 kV
SIENOPYR(120) (N)HX4GAF 0.6/1kV1×160,6/1 kV
SIENOPYR(120) (N)HX4GAF 0.6/1kV1×2.50,6/1 kV
SIENOPYR(120) (N)HX4GAF 0.6/1kV1×250,6/1 kV
SIENOPYR(120) (N)HX4GAF 0.6/1kV1×350,6/1 kV

Product details


E30 (N)HXH-J 3 × 120 mm² 0,6/1 kV

Product category: low voltage cables
Type: E30 (N)HXH-J
Rated voltage: 0,6/1 kV
Conductor material: CU
No. of cores: 3
Cross-section: 120 mm²
Conductor structure: RM
Reduced neutral: 70 mm²
Conductor structure: RM
Core insulation material: LSOH
Outer jacket material: LSOH
Nominal outer diameter: 43.0 mm
Approx. weight: 5160 kg/km
Resistant to…: heat
Appplication: indoor
Construction: Conductor Material bare copper, class 2, stranded (M) class 1, solid (E); Insulation: zero halogen elastomeric compound; Extruded inner covering; Outer sheath: flame retardant low smoke compound; Color code: 1 core: -O black 2 cores:-O blue, brown 3 cores:-J green-yellow, blue, brown 4 cores with reduced protective conductor:-J green yellow, brown, black, grey 4 cores:-J green-yellow, brown, black, grey 5 cores:-J green-yellow, blue, brown, black, grey Multi core:-J black with white numbers, one
Standard: DIN VDE 0266, HD 604
Available colours: orange
Fire performance: FE180 according to DIN VDE 0472-814; 90 minutes according to IEC60331-21
Leadfree
Halogen-free
Minimum installation temperature: -5°C
Application: Cables with the trade mark SIENOPYR-PLUS E30 can be used in indoor installation. In accordance to DIN 4102-12 the SIENOPYR-PLUS E30 cables have circuit integrity in case of fire ≥30 minutes. SIENOPYR-PLUS E30 cables shall be installed in accordance to the certificates (Allgemeine bauaufsichtliche Prüfzeugnisse - AbP).