Disclaimer: By using this website, you agree to the Terms and Conditions of Use (last updated 10/31/15).
×116 products match the given parameters.
All 0-9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Product category: | low voltage cables |
---|---|
Type: | E30 (N)HXH-O |
Rated voltage: | 0,6/1 kV |
Conductor material: | CU |
No. of cores: | 1 |
Cross-section: | 240 mm² |
Conductor structure: | RM |
Core insulation material: | LSOH |
Outer jacket material: | LSOH |
Nominal outer diameter: | 27.0 mm |
Approx. weight: | 2470 kg/km |
Resistant to…: | heat |
Appplication: | indoor |
Construction: | Conductor Material bare copper, class 2, stranded (M) class 1, solid (E); Insulation: zero halogen elastomeric compound; Extruded inner covering; Outer sheath: flame retardant low smoke compound; Color code: 1 core: -O black 2 cores:-O blue, brown 3 cores:-J green-yellow, blue, brown 4 cores with reduced protective conductor:-J green yellow, brown, black, grey 4 cores:-J green-yellow, brown, black, grey 5 cores:-J green-yellow, blue, brown, black, grey Multi core:-J black with white numbers, one |
Standard: | DIN VDE 0266, HD 604 |
Available colours: | orange |
Fire performance: | FE180 according to DIN VDE 0472-814; 90 minutes according to IEC60331-21 |
Leadfree | |
Halogen-free | |
Minimum installation temperature: | -5°C |
Application: | Cables with the trade mark SIENOPYR-PLUS E30 can be used in indoor installation. In accordance to DIN 4102-12 the SIENOPYR-PLUS E30 cables have circuit integrity in case of fire ≥30 minutes. SIENOPYR-PLUS E30 cables shall be installed in accordance to the certificates (Allgemeine bauaufsichtliche Prüfzeugnisse - AbP). |